Annicom Axio Logo  
    +44(0)1420487788  
 
home | about us | products | datasheets | account
 
   
datasheetdetails
 <<  |  <  |   AX-GS-CDRHT-D - Duct Carbon Dioxide and RH
AX-GS-CDRHT-D / Duct Mounted CO2 and RH&T Sensor POA Qty
 <<  |  <  | OVERVIEW | SPECIFICATION | DATASHEETS        

The AX-GS-CDRHT-D Duct Mounted CO2 and RH&T Transmitter uses NDIR single beam Infra-red technology to monitor CO2 concentration levels and output a corresponding 0-10V output. In addition the unit includes capacitive humidity and band gap temperature sensors. The unit is intended for use in return air ducts.
Product Features
• Duct mounting
• Monitors CO2 over range 0-2,000 ppm
• RH accuracy of 2.5%
• Lifetime calibration interval of CO2
• Gas permeable PTFE filters on both sensors
• Optional thermistor output for temperature

Power Supply
24Vac/dc +/-15% at 30mA average, 80mA peak
Ambient Temp. Range
0 to +50°C , 0-95% RH non condensing
Duct Air Velocity
0 - 450m/min
Analogue Outputs
0-10V at 10mA max
Sensor Type
Non-dispersive Infra-red
Range for 0-10V outputs
0-2000ppm CO2, Temperature 0-70°C, RH 0-95%
CO2 Calibration Interval
Lifetime (refer to ABC logic)
CO2 Accuracy
+/- 40ppm or 3% whichever is greater
CO2 Stability
Self Calibrating <2% FS over life of sensor (typical 10yrs)
CO2 Linearity
<1% FS @22°C
CO2 Settling Time
<2 minutes after power up (10 minutes maximum accuracy)
Housing
Flame retardant ABS (UL94-5VA)
Dimensions Housing
77 x 77 x 40 mm
Dimensions Probe
205 x 32 mm
Conformity
CE marked, EMC, LVD.
Country of Origin
UK

AX-GS-CDRHT-D.pdf / Duct carbon dioxide and RH&T sensor.